The question we get most often on WhatsApp — usually phrased as "just tell me which generator to buy" — deserves a better answer than a model number. Undersize and the genset trips or cooks itself every blackout; oversize and you pay tens of millions of rupiah extra upfront, then slowly damage the engine by running it at a fraction of its load. This guide shows you how we actually size villas, with the same numbers we use on surveys.

Step 1 — Add Up What Actually Runs

List everything that draws power during a blackout. Not the whole villa nameplate — the realistic simultaneous load. A typical 3-bedroom villa evening looks like: three air conditioners (800–1,200 W each running), a fridge and freezer (300 W), pool pump (750–1,100 W), water pressure pump (370–750 W), lighting (200–400 W LED), Wi-Fi, TV and chargers (150 W), and intermittent spikes from a kettle, microwave or hair dryer (up to 2,000 W each, briefly).

Running total for that villa: roughly 6–7 kW. If you stopped calculating here, you would buy an 8 kVA genset and regret it within a week. Here is why.

Step 2 — The Number Everyone Misses: Startup Surge

Motors do not start politely. An air-conditioner compressor draws roughly three times its running current for the first second or two; pool and well pumps behave the same. When PLN drops and your genset picks up the villa, several compressors may try to restart at the same moment — and that combined surge, not the steady evening load, is what your generator must survive without stalling or tripping.

The working rule we use: take your realistic running load, make sure the largest two or three motors can start on top of the rest, and keep 20–25% headroom above the result. Headroom is not waste — it is what stops the genset running at 100% (which shortens its life dramatically) and leaves room for the appliance you will inevitably add next year.

Typical Generator Sizes by Villa Type

PropertyTypical LoadRecommended Size
1–2 BR villa, fans, no pool2–3 kW5–8 kVA
2 BR villa, 2 AC, fridge, pumps4–5 kW10 kVA
3–4 BR villa, 4–5 AC, pool pump6–8 kW12–15 kVA
Large villa, 5+ BR, full AC, outdoor kitchen10–14 kW20–25 kVA
Guesthouse, 8–10 rooms18–25 kW30–40 kVA
Small hotel / restaurant35–60 kW60–100 kVA

These assume everything backed up. A cheaper strategy for large properties is a smaller genset feeding an "essentials" circuit — bedrooms' AC, fridges, pumps, lights, Wi-Fi — while the spa bathtub waits for PLN. We wire split circuits like this regularly during installation.

kVA vs kW — the 0.8 That Confuses Everyone

Generators are rated in kVA (apparent power), appliances in kW (real power). For typical villa loads the conversion is kW = kVA × 0.8. So a "15 kVA" genset delivers about 12 kW of real power. When a seller quotes you kVA and you compare it against your kW total without converting, you accidentally undersize by 20% — one of the most common mistakes in marketplace genset purchases.

Three Mistakes We Keep Seeing

Sizing to the MCB rating. Your 16,500 VA PLN connection is not your load — it is a ceiling. Most villas never approach it, and buying a genset to match it wastes serious money.

Ignoring the pool pump. It runs hours a day, it surges on start, and it is wired into a shed nobody thinks about. It belongs in the calculation.

Massive oversizing "to be safe". A 40 kVA unit carrying a 6 kW villa runs at 15% load forever — which causes wet stacking, fouled injectors and carbon buildup. Diesel engines want to work. Oversizing is not safety; it is slow damage you paid extra for.

Get the Calculation Done for You

Send us your appliance list — or just photos of your MCB panel and the appliances — and we will run the numbers and recommend a size in writing, free. Then compare our genset options and guide prices with anyone else's. The calculation stands either way.

Want It Handled by a Pro?

WhatsApp us your generator question or a video of the problem — free assessment, honest answer, same day.